Q-2, r. 4.1 - Clean Air Regulation

Full text
74. The operator of fuel burning equipment referred to in any of sections 64 to 67, with a rated heat capacity equal to or greater than 3 MW, and the operator of a stationary combustion turbine referred to in any of sections 68 to 70 must, at least once every 3 years, perform source emissions testing of the gases emitted into the atmosphere by the equipment or turbine, calculate the rate or concentration of the contaminants referred to in those sections, and for that purpose, measure each of the parameters necessary for the calculation.
In addition, the operator must carry out the first sampling and calculation within 1 year as of 30 June 2011 in the case of an existing equipment or turbine or, in the case of new equipment or turbine, within 1 year as of the date on which the equipment or turbine is put into operation.
O.C. 501-2011, s. 74.